Echelon LonWorks Twisted Pair Control Module User Manual

Page 31

Advertising
background image

LonWorks Twisted Pair Control Module User's Guide

23

transceivers, or TPM-1250 SMX transceivers to eliminate the possibility of

reflection-related transmission failures. No such topology rule applies to the

use of TP/XF-78 control modules, TPT/XF-78 transceivers, or TPM-78

SMX transceivers.
Referred to as the “8-in-16” topology rule, this rule requires that no more than 8

TP/XF-1250 Control Modules, TP/XF-1250 Transceivers, or TPM-1250 SMX

Transceivers be located within any 16 meter length of cable. This means that no

matter where along the bus the 16 meter measurement is taken, there should be

no more than 8 devices. Figure 11 provides a diagram of such a measurement

technique. In the figure, the numbers in the boxes represent the number of

devices connected to the bus and the “T” represents the bus termination.

Figure 11. 8-in-16 Topology Rule Example

In the example, we see an installation with six groups of devices, varying in

number from 2 to 8 devices, in a doubly terminated bus. By using a 16 meter

measurement stick that we can move from side-to-side over the length of the bus,

we can determine whether the 8-in-16 rule has been met (designated by the word

“OK”) or violated (shown by the designation “PROBLEM”). In the case of the

PROBLEM area, a total of 13 devices are located within a 16 meter length of the

bus, which amounts to five more devices than are permitted under the 8-in-16

rule.
There are two solutions that can be applied to situations in which the 8-in-16 rule

has been, or must be, violated by the installation scenario. The first and simplest

remedy is to insert a router and two termination networks in the bus to break the

network into two channels (see Figure 12 on page 24). Because each side of the

router comprises a different channel, the bus is effectively split and the devices

divided between two channels.

Advertising