Installing the LPR Router

Modules

Table 11.1 LPR Router Wiring Connections

Screw Terminal

Wiring Connection

1 and 2

Incoming network wiring, polarity-insensitive - CHANNEL A

3 and 4

Outgoing network wiring, polarity-insensitive - CHANNEL A

5 and 14

Cable shields - terminals 5 and 14 are internally connected.

6 and 7

Incoming power wiring, 16-30VAC or VDC, 2.0VA, polarity-
insensitive. If using DC power, it is good practice to maintain
continuity of the power polarity throughout the network. Terminals 6
and 8 should be the same polarity, and terminals 7 and 9 should be
the same polarity.

10 and 12

Unused
Jumpered together internally - may be used to land extra wires

11 and 13

Unused
Jumpered together internally - may be used to land extra wires

15 and 16

Incoming network wiring, polarity-insensitive - CHANNEL B

17 and 18

Outgoing network wiring, polarity-insensitive - CHANNEL B

Table 11.2 LonPoint LPR Router Module Specifications

Function

Description

Processor

Two Neuron 3150 Chips, 10MHz

Service function

Recessed service switch, service LED. Dual tear-off bar-code Neuron

ID self-adhesive tag for application to red-line drawings in the field

Transceiver type

Varies by model

Network connector

Two phone plug connectors accessible from front panel - one per

channel

Input power

16-30VAC or VDC @ 2.0VA, internally isolated power supply

Mounting

Type 2 or Type 2D Base Plate

Temperature

-40 to +85°C, operating and non-operating

Humidity

10 to 95% RH @ 50°C

EMI

FCC A, CE Mark

Safety agency

UL 916