Network Cabling and Base Plate Installation

Power Cabling Requirements in AWG (Continued)

Load (VA)

Feet

10

15

20

25

30

40

55

75

100 130 180

200

340

22

22

22

20

20

18

18

16

14

14

12

12

365

22

22

22

20

20

18

16

16

14

14

12

12

375

22

22

22

20

20

18

16

16

14

12

12

12

395

22

22

20

20

20

18

16

16

14

12

12

400

22

22

20

20

18

18

16

16

14

12

12

420

22

22

20

20

18

18

16

14

14

12

12

470

22

22

20

20

18

18

16

14

14

12

475

22

22

20

20

18

16

16

14

14

12

500

22

22

20

18

18

16

16

14

12

12

545

22

20

20

18

18

16

16

14

12

12

580

22

20

20

18

18

16

14

14

12

12

595

22

20

20

18

18

16

14

14

12

630

22

20

18

18

18

16

14

14

12

635

22

20

18

18

16

16

14

14

12

750

22

20

18

18

16

16

14

12

12

755

20

20

18

18

16

14

14

12

12

795

20

20

18

16

16

14

14

12

865

20

18

18

16

16

14

14

12

945

20

18

18

16

16

14

12

12

1000

20

18

16

16

16

14

12

12

1010

20

18

16

16

14

14

12

12

1190

20

18

16

16

14

14

12

1200

18

18

16

16

14

12

12

1260

18

18

16

14

14

12

12

1375

18

16

16

14

14

12

12

1500

18

16

16

14

14

12

1590

18

16

14

14

14

12

1645

18

16

14

14

12

12