Ir enclosure, Ir mounting – ENMET EX-6165 User Manual
Page 6
 
EX-6120, 6165 SERIES IR
ENMET Corporation
3
3.0 Installation of the EX-6120, 6165 S
ERIES
IR
C
AUTION
:
Area must be declassified during installation.
The
EX-6120, 6165 S
ERIES
IR
gas sensor/transmitter (S/T) is a 3-wire, 24
V
DC
4-20 mA S/T for the detection of
combustible gas. The S/T is meant to be used in conjunction with an appropriate power supply and controller. The
EX-
6120, 6165 S
ERIES
IR
sensor/transmitter is in an enclosure rated for use in area listed below:
Certificate Numbers
IECEx SIR08.0009X,Code EX d IIC 
SIRA 08atex1031x, Code EX d IIC 
Standards
IEC 60079-0 : 2004 (Edition 4) 
EN 60079-0 : 2006 
IEC 60079-1 : 2007-4 (Edition 6) 
EN 60079-1 : 2007 
Temperature Codes
T4 (Ta-20 to +60 deg C)
Zones
1 & 2
Equivalent Rating
Class I, Division 1, Group A, B, D & D
Appropriate wiring, conduit and fittings are required for proper installation in an explosion proof rated environment.
C
AUTION
:
Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of gas,
the density of the gas, locations where the gas may be confined and locations where the gas may damage or 
injure property or personnel, when choosing locations of sensor/transmitters. 
Take into consideration environmental factors when deciding on S/T location. Avoid locations where the S/T may be 
damaged by liquid immersion, excessive heat or other known hazards. Also, take precautions to insure condensation 
inside of the conduit does not enter the S/T. 
3.1 Mounting the EX-6120, 6165 S
ERIES
IR Enclosure
Mount the enclosure, using the two mounting holes provided see Figure 2. Pay particular attention to the source and 
density of the gas being detected when choosing the location. Mount the S/T near the ceiling for lighter than air gases 
/vapors and near the floor for heavier then air gas/vapors. Contact 
ENMET
if you have questions regarding your
application.
C
AUTION
:
Before connecting S/T to controller remove the power source to controller. Failure to do so may cause damage
to sensitive components.
Figure 2: EX-6120, 6165 S
ERIES
IR Mounting
Approximate Measurements in Inches (mm)
Maximum Depth = 5 Inches (127mm)
Optional 
Conduit fitting 
Typically: 3/4
″
NPT female
4.96 (126) Centers
4.53 (115)
9
.8
4
(
2
5
0
)
7
.4
8
(
1
9
0
)
2 x 0.27 (2 x 7) dia.
Mounting Holes
Optional Weatherguard
Inlet/Outlet
Port 1 of 2
Display
Menu Switches
Power & Alarm LEDs
Inlet/Outlet 
Port 1 of 2 
MENU UP DOWN ENTER