0020096324_01.1 - 09/10 - Glow-worm

- 12 -

• Run

the

fi lling pump until the pipe (8) is completely purged.

• Close the air bleed on the heat pump.

• Close the valve (7) and pressurize the glycol water circuit to

between 1.5 and 2 bar using the pressure gauge (6).

• Close the valve (5) and stop the fi lling pump.

i

The glycol water level may reduce during the fi rst
month after commissioning the installation. It can
also vary according to the temperature of the heat
source.

Any residues of glycol water must be stored in an appropriate
container and used for the next refi ll.

• Give the container of glycol water residue to the user.

8 Electrical

connections

e

Incorrect installation can cause electric shock or
appliance damage. The electrical connection of
the appliance must be made only by a qualifi ed
engineer.

i

Extra protection may be required at installation to
ensure voltage class II.

The external wiring must be earthed, with correct polarity and in
accordance with current standards.

i

Equipment compliant with CEI 61000-3-12.
Equipment compliant with CEI 61000-3-11.

The manufacturer declines any responsibility for damages to
persons or others caused by the incorrect installation of the
appliance earthing. This includes failure to comply with current
standards.

Component

Voltage

(

cable section

minimum

)

Power cable

230 V (3 x 0.75 mm²)

E-bus cable

24 V (2 x 0.75 mm²)

E-bus connection

1

Key
1 E-bus

connector

9 Commissioning

• Refer to the system’s installation manual in order to

commission the installation

.

Pump fl ow / pressure curve

60

50

40

30

20

10

0

200

400

1000

800

600

1200 1400

B

2

1

4

3

Key
1

Speed II by-pass closed

2

Speed II by-pass open

3

Speed I by-pass closed

4

Speed I by-pass open

A

Available pressure (kPa)

B

Flow in the circuit (l/h)

9.1

Setting the pump speed selector

1

2

3

Key
1 Speed

selector

2

Speed I

3

Speed II

• Turn the selector (1) to select pump speed I or II according to

the fl ow/pressure curve above.