Installation, Continued, Floor clearances – Desa FVFM27NR/PR User Manual

Page 9

Advertising
background image

108382-01E

9

9

For more information, visit www.desatech.com

For more information, visit www.desatech.com

Area of Various Standard Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

INSTALLATION

Continued

FLOOR CLEARANCES

A. If installing appliance on the floor level, you must maintain

the minimum distance of 14" to combustibles (see Figure 8).

B. If combustible materials are less than 14" to the fireplace, you

must install appliance at least 5" above the combustible flooring
(see Figure 9).

NOTICE: If your installation does not meet the mini-
mum clearances shown, you must do one of the
following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel

Figure 7 - Minimum Mantel Clearances When Using Hood

Minimum Non-
Combustible
Material

8"
Min.

12"

15"

18"

All minimum
distances are
in inches

20"

2

1

/2

"

6"

8"

10"

12"

Distances to
Underside of
Mantel

Hood
(GA6050, GA6052)

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

Figure 8 - Minimum Fireplace
Clearances If Installed at Floor
Level

Figure 9 - Minimum Fireplace
Clearances Above Combus-
tible Flooring

14"
Min.

Combustible
Material

Noncombustible Material

Hearth

5"
Min.

Combustible
Material

Hood (GA6050,
GA6052 or GA6053)

NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.

INSTALLING DAMPER CLAMP ACCESSORY
FOR VENTED OPERATION

Note:

When used as a vented heater, appliance must be installed

only in a solid-fuel burning fireplace with a working flue and
constructed of noncombustible material.

If your heater is a manually controlled model, you may use this
heater as a vented product. There are three reasons for operating
your heater in the vented mode:
1.

The fireplace does not meet the clearance to combustibles re-
quirements for vent-free operation

2.

State or local codes do not permit vent-free operation

3.

You prefer vented operation

If reasons number 1 or 2 above apply to you, you must permanently
open chimney flue damper. You must install the damper clamp
accessory (to order, see Accessories, page 24). This will insure vented
operation (see Figure 10). The damper clamp will keep damper open.
Installation instructions are included with clamp accessory.

See chart below for minimum permanent flue opening you must
provide. Attach damper clamp so the minimum permanent flue
opening will be maintained at all times.

Chimney Height (ft.) Minimum Permanent Flue Opening

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

Figure 10 - Attaching Damper Clamp

Damper

Damper
Clamp

Damper
Clamp

Damper

Damper

Masonry Fireplace

Manufactured Fireplace

INSTALLATION

Mantel Clearances (Cont.)

Floor Clearances

Installing Damper Clamp Accessory for Vented Operation

Determining Minimum Mantel Clearance When
using a Hood

If minimum clearances in Figure 6, page 8 are not met, you must
have a hood. When using a hood there are still certain minimum
mantel clearances required. Follow minimum clearances shown in
Figure 7 when using hood.

Advertising