INSTALLATION

Continued

* A CSA design-certified equipment shutoff valve

with 1/8" NPT tap is an acceptable alternative to

test gauge connection. Purchase the optional CSA

design-certified equipment shutoff valve from your

dealer. See Accessories, page 26.

Figure 15 - Gas Connection

Install sediment trap in supply line as shown in

Figure 15. Locate sediment trap where it is within

reach for cleaning. Locate sediment trap where

trapped matter is not likely to freeze. A sediment

trap traps moisture and contaminants. This keeps

them from going into heater controls. If sediment

trap is not installed or is installed wrong, heater

may not run properly.
IMPORTANT:

Hold the pressure regulator with

wrench when connecting it to gas piping and/or

fittings. Do not over tighten pipe connection to

regulator. The regulator body could be damaged.

Pressure
Regulator

Test Gauge Connection*

Tee
Joint
Pipe
Nipple
Cap

3/8" NPT
Pipe Nipple

Heater
Cabinet

Sediment

T

rap

Equipment
Shutoff
Valve *

3"
Min

Natural Gas

From Gas Meter

(4" W.C. to 10.5" W.C.

Pressure)

Propane/LP From External

Regulator (11" W.C. to 14"

W.C. Pressure)

Ground Joint
Union

Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

large enough diameter to allow

proper gas volume to heater. If

pipe is too small, undue loss of

volume will occur.

Typical Inlet Pipe Diameters

20,000 Btu/Hr Models - 3/8" or greater
30,000 Btu/Hr Models - 1/2" or greater

Installation must include equipment shutoff valve,

union and plugged 1/8" NPT tap. Locate NPT tap

within reach for test gauge hook up. NPT tap must

be upstream from heater (see Figure 14).
IMPORTANT:

Install an equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged heater valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

Figure 14 - External Regulator With Vent

Pointing Down

External
Regulator

Propane/LP
Supply Tank

Vent
Pointing
Down