OPTI-UPS DS3000B-RM User Manual

Page 12

Advertising
background image

15

Fig. 3 Example of Installation

5.4 Default settings at the factory

On the LCD display you will find several of the UPS parameters to select.
Default settings are as follows:

Settings Selection

Factory

default

100/110/115/120/127
Vac

120V (FOR 1x0 series)

Output Voltage Setting

208/220/230/240 Vac 230V (FOR 2x0 series)

Input/Bypass Voltage

±10%

+10/-15%

+15/-20%

+10/-15%

Input/Frequency

±2%

±5%

±7%

±5%

HE Mode Setting

On/Off

Off

Free Run Mode

On/Off

On

Bypass Enable/Disable at free run mode Disable/Enable

Disable

Alarm silence

On/Off

Off

Site wiring alarm

Enable/Disable

Disable

External Battery pack setting

0, 1, 2

0

You may change default settings, but we recommend that this is done after installation and
before starting up loads. Read UPS configurations in chapter 7.2 for more information.

16

6. Computer and Alarm connections

At the back of the UPS is an interface allowing direct communication with your computer
system, the location of which can be found in figure 2. There is a RS232 serial data interface,
one USB data interface and an emergency power off switch supplied. However, the RS232
port cannot be used when the USB interface is in use.

In addition there is an optional interface slot that allows you to install different
communications cards. It can be used parallel with either the RS232 or USB ports.

Currently there are two cards available for the optional interface slot. An SNMP/WEB card
allows management and monitoring over a network or internet, and the AS/400 card allows
voltage free relay contacts. Your local dealer will have more information about these option
cards.

Connecting the UPS to a Computer

The communication device for the UPS and PC comes as a complete package with power
management software. Only the communication cable provided with UPS may be used to
connect to your computer, which is accomplished through the UPS RS232 port. Also ensure
that the operating system on your computer is supported. Instructions provided in the power
management software will help with this installation.

Other advanced power protection solutions such as SNMP are provided by your dealer.

RS-232 Standard Interface port

The RS-232 interface uses a 9-pin female D-sub connector. This information consists of data
about utility, load and the UPS. The interface port pins and their functions are identified in
the following table.

Pin #

Signal name

Direction (re UPS)

Functions

2 TxD Output

TxD

Output

3

RxD

Input

RxD / Inverter Off Input

5 Common

Common

6

CTS

Output

Ac Fail Output

8

DCD

Output

Low Battery Output

9

RI

Output

+8-24 VDC Power

Caution! Max rated values 24Vdc/50mA