Ce marked units – SOR Single Point Ultrasonic Level Switch User Manual

Page 10

Advertising
background image

10/20

Form 771 (08.13) ©SOR Inc.

Model Number

Accessory Designator

I.S. CI, FI or AI

Expf FM or CS

Non-Agency (no match)

721

 2-N-P9-G

5003-009

5003-010

5003-010

721

 2-N-P9-C

5003-011

5003-012

5003-012

721

 2-V-P9-C

__

__

5003-028

721

 2-E-P9-C

__

__

5003-042

NOTE: When ordering replacements for remote units (R in the 4th position of the model
number), supply cable length information and serial number. Circuit boards are tuned
to remote cable length for optimum circuit performance.

CE Marked Units

In order to achieve the stated accuracy of +/-1mA, a shielded cable, cable gland and shield
beads must be used. SOR recommends using a shielded cable made of PVC insulation
around a tinned copper braid shield. (Olflex CY cable or equivalent.) Refer to illustrations
below for installation of shield beads.

Probe Wire Shield Bead

Short/Fat Bead

Long/Slender

Bead

2 Loops

Positive

Negative

Install end of bead as close

to cable gland as possible

2 Loops

Probe Wire Shield Bead

Discharge the sensor. Connect the center conductor and shell of sensor wire end as

shown on page 5. (See

)

Connect the sensor plugs to the new board. The sensor wire (T) plugs into J2

(transmit). The sensor wire (A) plugs into J1 (receive).

Replace the two mounting screws into the plastic ring. These screws are self-tapping.

Do not overtighten.

Replacement Circuit Boards Match the characters of your model number with those
shown below to select the proper replacement board part number. Accessory
designators are located at the end of the model number in no particular order.