Form 771 (08.13) ©SOR Inc.

7/20

Electrical Connection (Intrinsically Safe)

Intrinsically Safe Models (does not apply to viscous or epoxy controls and sensors):

Any model numbers containing the designators “AI”, “CI” or “FI” are listed Intrinsically
Safe with CSA (AI), CENELEC (CI) or FM (FI). Please note the housing nameplate to deter-
mine the Agency Approval of your instrument. Connections must be as shown on the SOR
Control Drawings shown on pages 8-12.

AI CSA Intrinsically Safe... ................Class I, Div. 1, Groups C, & D; Class II, III, Div. 1,

Groups E, F, & G; Class I, Div. 2, Groups A, B, C, D; Class II, III, Div. 2, Groups F, G;

Type 4X; T4

Connections must be as shown on the SOR Control Drawing 9065-136.

CI CENELEC Intrinsically Safe...... ....................................................EEx ia IIB T4, IP65

Connections must be as shown on the SOR Control Drawing 9065-146.

FI FM Intrinsically Safe....... ............................................Class I, Div. 1, Groups C, & D;

Class II, III, Div. 1, Groups E, F, & G; Class I, Div. 2, Groups A, B, C, D;

Class II, III, Div. 2, Groups F, G; NEMA 4X; T4

Connections must be as shown on the SOR Control Drawing 9065-135.

Electrical Connection (CE Marking)

Shield Beads
Three beads are included with your CE marked unit. Two of the beads are 5/8” dia. x 1/2”
long; they are used in the sensor installation. (See page 3.) The other bead is 3/8” dia. x
3/4” long. Use this bead for the following electrical connection.

In order to achieve the stated accuracy of ±1mA, a customer supplied shielded cable and
cable gland are used with the furnished 3/8” dia. x 3/4” bead. SOR recommends using a
shielded cable made of PVC insulation around a tinned copper braid shield (Olflex CY or
equivalent). Install the bead as close as possible to the cable gland.

Strip outer cable insulation and shield approx.

10

inches.

Separate the positive and negative wires.

Slide the bead over both wires.

Wrap each wire around opposite sides of the bead

to make two complete loops. (See

)

Make internal power connections as shown on page 4.

Install the cable gland per manufacturer’s instructions. The cable gland will provide

necessary grounding for the cable shield.

Install bead as close as
possible to cable gland