Electrical Specifications

Relay Output Specifications

Description

2 channel relay output module.

Relay
Functionality

Form A normally open

Output Current
Rating
(at rated
power)

Resistive load at up to 30° C
10A @ 5-30V dc
10A @ 125V ac
10A @ 250V ac

Resistive load at up to 65° C
6A @ 5-30V dc
6A @ 125V ac
6A @ 250V ac

Output Power
Rating
(Resistive

Resistive load at up to 30° C
300W Maximum for 30.0VDC
1250VA Maximum for 125VAC
2500VA Maximum for 250VAC

Inductive Loads

1

UL Pilot
Duty Contact
Ratings (Power
factor 0.35 or
less for AC):






























Additional UL
ratings:

AC Contact Rating

Code Designation

Thermal

continuous test

current (A)

Max. current (A)

a,b

Max. VA

120 VAC

240VAC

Make

Break

Make

Break

Make

Break

B300

5

30 3 15 1.5

3600 360

Notes:

a

Power factor 0.35 or less

b

For maximum ratings at voltages between the maximum design value and 120 volts, the maximum

make and break ratings are to be obtained by dividing the volt-amperes rating by the application
voltage. For voltages below 120 volts, the maximum make current is to be the same as for 120 volts,
and the maximum break current is to be obtained by dividing the break volt-amperes by the application
voltage, but these currents are not to exceed the thermal continuous test current.

DC Contact

Rating Code

Designation

Thermal

continuous

test current

(A)

Max. make/break current (A)

c,d

Max. make / break

VA

125 VDC

250VDC

R150 1.0 0.22

-

28

R300 1.0 0.22 0.11

28

Notes:

c

The maximum make and break ratings are to be obtained by dividing the volt-ampere rating by the

application voltage, but the current values are not to exceed the thermal continuous test current.

d

Inductive loads as specified in Section 8.2.7 of Industrial Control and Systems; Control Circuit and Pilot

Devices, ANSI/NEMA
ICS5-1993.


1/3 hp, 125 V ac, 250V ac
30V dc Make / Break 2A (Pilot Duty)
250V ac, Make 20A / Break 2A (Pilot Duty)
2A, 250V ac, Tungsten Lamp
2A, 30V dc, Tungsten Lamp

1

Connecting surge suppressors across your external load will extend the life of the relay

contacts.