Active LED Does Not Illuminate

Possible Causes

The module is not communicating with the PLC rack.

Corrective Action

1. Deinstall the module. See chapter 2, “Installation and Wiring.”

2. Place the rack in run mode.

3. Reinstall the module in the rack. See chapter 2, “Installation and Wiring.”

Fault LED Does Not Illuminate

Possible Causes

Module self-test error

Fatal hardware error

Corrective Action

Contact your local distributor.

Fault LED Blinking Red

Possible Causes

Type of self-test error. Possible codes are indicated in the Diagnostic LEDs section of chapter 1, “Overview.”

Corrective Action

Verify module configuration information.

No Signal Indication

There is no indication of a signal in the input register count rate word. If status bit 3x+1 - 3x+8 (Bit 14)
(counter input state) is high and status bit 4 (rate zero) is high.

Possible Causes

If you have an open collector output or a relay or contact type output, you might require a 1 to10 kohm pull-
up / pull-down resistor.