VENTING INSTALLATION

INSTRUCTIONS

Continued

Note: Install
restrictor into
inner collar of
fireplace as
shown.

Venting with Two 90° Elbows

Vertical (V

1

)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Vertical (V

1

) + Vertical (V

2

) = 40' max.

Figure 23 - Vertical Venting

Configuration Using Two 90° Elbows

(Vertical Round High Wind Termination

Shown)

45° Elbow

Vertical Venting

V = 40' max.

Figure 24 - Vertical Venting Configuration

With No Horizontal Run (Vertical Round

High Wind Termination Shown)

Note: Install
restrictor into
inner collar of
fireplace as
shown.

45° Elbow

HIGH ALTITUDE INSTALLATION

Your DESA direct-vent fireplace has been tested and

approved for elevations from 0-2000 feet (USA) and

elevations from 0-4500 feet (Canada).

Fireplaces for High Altitude (models ending in

-HA) are for installation above 4000 feet only.

These fireplaces are equipped with parts specific

for higher altitudes. IMPORTANT: These fireplac-

es can NOT be converted to Propane/LP gas.

When installing a non-high altitude fireplace at an

elevation above 2000 feet (in the USA), you may

need to decrease the input rating by changing the

existing burner orifice to a smaller size. Reduce

input 4% for each 1000 feet above sea level. Check

with your local gas company for proper orifice

size identification.

When installing this fireplace at an elevation above

4500 feet (in Canada), check with local authorities.
IMPORTANT:

For horizontal installations

above 2,000 feet, it is recommened that a 12"

extension pipe be added before starter elbow

(see Figure 25, page 18) and a round horizontal

termination be used.