The Aurora Unitary Protocol Converter (UPC) is designed 
to add-on to any Aurora based heat pump control. The 
Aurora Unitary Protocol Convertor (UPC) is designed 
to allow water source heat pumps to be integrated into 
Building Automation Systems (BAS) with ease. The 
Aurora UPC is an integrated solution and communicates 
directly with the Aurora Heat Pump Controls and allows 
access/control of a variety of internal Aurora heat pump 
operations such as sensors, relay operation, faults and 
other information. In turn, the UPC then converts internal 
Aurora Modbus protocol to BACnet MS/TP, LON, or N2 
protocols and communicates to the BAS system. This 
provides the great benefit of complete control integration 
and a myriad of information available to the BAS from 
the heat pump control. Plus it also allows individual unit 
configuration such as ECM fan speeds or freeze protection 
setting directly over the BAS without the need for access 
to the actual heat pump. The Aurora UPC is programmed 
using the powerful Eikon object oriented.
The Aurora UPC is implemented with the Aurora Base 
Controller (ABC) heat pump control into our latest water 
source heat pumps. This will allow for a BAS to integrate 
and communicate to the heat pump thru a choice of 3 
different communication protocols. The Aurora UPC has 
the ability to communicate BACnet MS/TP, N2 open, or 
LonWorks (requires LON Plugin card). This flexibility is 
possible due to the onboard dipswitches which allow for the 
desired protocol and baud rate to be selected in the field. 
All zone temperatures and zone sensors are connected 
to the UPC on an RNet bus, simplifying hook up at the 
unit. RNet sensors can include a combination of zone 
temperature and humidity, CO2, and VOC sensors. The 
UPC includes built-in support for a custom configurable 
keypad/display unit - BACview6 (4-line by 40 character 
per line display) or BACview5 (2-line by 16 character per 
line display). Up to 2 Keypad/display units can be mounted 
remotely for configuration and troubleshooting.
There are an extensive number of points that the UPC has 
available over the network for integration into the BAS. 
Control programmers need to carefully determine which 
points they want to add into the BAS database. A list of 
the BACnet points, N2 points, and LON SNVTs are available 
along with their individual point descriptions by contacting 
the Commercial Solutions Group at 1-877-677-4420. 