Unit display and interface cont, Mui menu navigation – WaterFurnace Envision Hydronic (NDW) User Manual

Page 24

Advertising
background image

24

NDW INSTALLATION MANUAL

Unit Display and Interface cont.

MUI Menu Navigation

Welcome

Info Temp Stat Outputs Settings Maint Alarm_History

Dual Stage

Info

Outputs

Comp1 Status

ON

Comp2 Status

OFF

Acc1 Status

OFF

Stg1 Status

Normal

Stg2 Status

Normal

BO7 OFF
BO8 OFF
BO9 OFF
EXPB01 OFF
EXPB02 OFF
EXPB07 OFF
EXPB08 OFF

Outputs

Status

Unit Status

Auto

Y1 Status

OFF

Y2 Status

OFF

O Status

OFF

Emerg Shutdown OFF
Current Sens1

OFF

Current Sens2

OFF

Load Flow

OFF

Src Flow

OFF

Low Pres1

ON

Hi Pres1

OFF

Low Pres2

ON

Hi Pres2

ON

Comp1 Low Limit NML
Comp2 Low Limit NML

Stat

Temperatures

Enter Load

77.2°F

Leave Load

51.0°F

Enter Source

70.0°F

Leave Source

66.0°F

Source Frz1

77.8°F

Source Frz2

30.0°F

Load Frz1

30.0°F

Load Frz2

30.0°F

Src Frz Setpt

30.0°F

LD Frz Setpt

30.0°F

Temp

Settings

Unit of Measure F

Settings

Water-to-Water
PRODCWWE-08B
MM/DD/YY

Maintenance

Y1 Input

Auto

Y2 Input

Auto

O Input

Auto

Emerg SD

Auto

Acc1 Sel

ON Comp

Lead/Lag Select OFF
Low Frz Setpt

15°F

Hi Frz Setpt

33°F

Acc1 Dly

9 S

Maint

ALARM SUMMARY

^/High Pressure

Alarm

Alarm lock-outs are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds.

Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.

Advertising