Troubleshooting, Cleaning and maintenance – Desa (V)T36ENA User Manual

Page 31

Advertising
background image

www.desatech.com

111251-01E

31

TROUbLEShOOTING

WARNING: Turn off heater and let cool before servicing. Only a

qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean

pilot. This can damage pilot unit.

The two most common causes of a malfunctioning gas appliance are:

1. Loose wiring connections

2. Construction debris clogging the pilot and/or gas control valve filter

Note:

Before troubleshooting the system, make sure the gas shutoff valve is ON.

OBSERVED PROBLEM

Ignitor will not spark or pilot will

not light

POSSIBLE CAUSE

1. No gas supply, or shutoff valve

is OFF

2. Air in gas line

3. Construction debris clogging

pilot orifice

4. Low gas pressure

5. Kinked pilot line

6. Control valve knob is not

opening

7. No power to unit or the igni-

tion module or power trans-

former is bad

8. Vent damper not fully open

REMEDY

1. Check to see if you have gas

supply and that equipment

shutoff valve is opened

2. Repeat lighting procedure sev-

eral times to purge all air out of

lines. If after repeated attempts

appliance does not light, call for

qualified service and repair.

3. Remove debris and dirt, in-

spect and clean any other

possible obstructions

4. Contact your gas supplier to

check pressure

5. Have a qualified technician

replace pilot line

6. Replace control valve (Refer to

Replacement Parts, page 38)

7. Check that main power is on

and that all wire connections are

made correctly to the ignition

model (see Wiring Diagram,

page 27). Check for 24 VAC at

the secondary side of the trans-

former. If 24 VAC is present,

and module does not operate,

have module replaced otherwise

have transformer replaced.

8. Open vent damper until fully

locked in OPEN position

CLEANING AND MAINTENANCE

Continued

vENTING SYSTEM

Conduct annual inspection of the venting system

following these guidelines:

1. Check areas of venting system that are ex-

posed to the weather for corrosion (rust spots

or streaks and, in extreme cases, holes). Have

these items replaced immediately by a quali-

fied service person.

2. Remove the vent cap and shine a flashlight

into the vent. Remove any foreign material.

3. Check for evidence of excessive condensation.

Continuous condensation can cause corrosion

of caps, pipes, and fittings and can be caused

by having excessive lateral runs, too many

elbows, or exterior portions of the system

being exposed to cold weather.

4. Inspect joints to verify that no pipe section or

fitting has been disturbed and loosened. Check

mechanical supports such as wall straps for

rigidity.