4

FORM NO. L-21208-C-0908

RSTC1000 MODBUS REGISTERS

All values written to or read from the RSTC1000 must be in Imperial units. Conversion of values from other units of
measure are done within the HMI or PLC.

The following Modbus registers are numbered per the Modbus standard. Many PLCs use an alternate numbering
scheme and the Modbus register numbers can be converted to the PLC numbering scheme by adding 40,001 to each
Modbus register number.

Common Defi nitions and Abbreviations:

lsb:

least signifi cant byte

msb:

most signifi cant byte

lsw:

least signifi cant word

msw:

most signifi cant word

byte:

8 bits, 0-255 range

word: 2 bytes, 0-65535 range

P

RODUCT

I

NFORMATION

1 – 4: Product Name Sent as ASCII values, read only.
Example:

RSTC1000

Register 1: R (msb), S (lsb)

Register 2: T (msb), C (lsb)

Register 3: 1 (msb), 0 (lsb)

Register 4: 0 (msb), 0 (lsb)

6 – 7: Product Number Sent as long integer, read only.
Example:

964523

Register 6: 14 (msw)

Register 7: 47019 (lsw)

964523 = (14 * 65536) + 47019

8 – 9: Serial Number Sent as long integer, read only.
Example:

1234567

Register 8: 18 (msw)

Register 9: 54919 (lsw)

1234567 = (18 * 65536) + 54919

10 – 11: Software Part Number Sent as long integer, read only.
Example:

12345

Register 10: 0 (msw)

Register 11: 12345 (lsw)

12345 = (0 * 65536) + 12345

12: Software Revision Sent as ASCII value, read only.
Example:

A

Register 12: 0 (msb), 65 (lsb)