CALIBRATION AND ADJUSTMENT

FIGURE 7

End of

Travel

LED

Auto

Indicator

Fine

Adjustment

Control

Manual

Push

Buttons

Mode

Switch

Sensor

Select

Switch

Power

Switch

FIGURE 8

LAMP

PHB1

GAIN 1

PHB2

GAIN 2

OUTPUT

F. ADJ

C. ZERO

C. GAIN

NOR/REV

Switch for

MANUAL

Operation

NOR/REV

Switch for

CENTER

Operation

NOR/REV

Switch for

AUTO

Operation

Error

Indicator

SENSOR CALIBRATION

EPC Calibration

1. Set Fine Adj. Pot on the front panel to 5.0 (mid-travel)

(See Figure 7).

2. Using the Sensor Select Switch located on the front

panel, select either the RIGHT or LEFT Sensor (See

Figure 7).

3. Insert a piece of material until it completely covers the

sensing area of the sensor; then, remove the material.

The Error Indicator array will light up to show

maximum and minimum insertion with up to five red

lights on either side of the center green light (See

Figure 7).

NOTE: Use opaque material with PH16 and PH46

and soundproof material with the UH21 and

UH01.

4. Rotate the Photo Head Balance Pot (PHB for the

left sensor and

PH2B for the right sensor) until the

insertion and removal of material lights up an equal

number of red lights on either side of the green light

on the Error Indicator array (See Figures 7 and 8).

5. Rotate GAIN  for the left sensor and GAIN 2 for the

right sensor until the insertion of material illuminates

five red lights in either direction (See Figures 7 and 8).

CPC Calibration

1. Perform EPC Calibration separately for each sensor.

2. Set the Sensor Selector Switch to the CPC position

(See Figure 7).