When connecting electrical power and control
wiring to the unit, waterproof type connectors
must be used so that water or moisture cannot
be drawn into the unit during normal operation

.

CAUTION

Power supply to the unit must be N.E.C. Class 1, and must
comply with all applicable codes. A fused disconnect switch
should be field provided for the unit. The switch must be
separate from all other circuits.

Figure 5

Electrical Access

Heater Power Entry

Thermostat

Entry

Line Voltage

Entry

Unit must be grounded in accordance with
national and local codes. Failure to ground unit
properly can result in personal injury or death.

WARNING

Figure 6

Typical Wiring Connections

R

R

C

C

C

C

R

R

L2

L1

Y

Y

Y1

Y

L1

L2

L3

POWER WIRING

208/230-1-60

(90°C MIN. WIRE)

POWER WIRING

24V CONTROL WIRING

(NEC CLASS 2)

TYPICAL WIRING CONNECTION

1 PHASE

GROUND
SCREW

THERMOSTAT

OUTDOOR UNIT

THERMOSTAT

OUTDOOR UNIT

GROUND
SCREW

POWER WIRING

200/230-3-60, 460/575-3-60

(90°C MIN. WIRE)

24V CONTROL WIRING

(NEC CLASS 2)

POWER WIRING

TYPICAL WIRING CONNECTION

3 PHASE

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON 15, 20 & 25 KW MODELS.

* 5 & 10 KW HEATER ACCESSORY FUNCTION OFF

W1 ONLY.

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON 15, 20 & 25 KW MODELS.

* 10 KW HEATER ACCESSORY FUNCTION OFF

W1 ONLY.

ECONOMIZER

NOT

INSTALLED

ECONOMIZER

W1

W

W

W1

G

G

G

G

W2

Y2

W2

O

O

O

O

BLUE

WHITE

YELLOW

ORANGE

GREEN

BLACK

Do not connect connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

Do not connect connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram. Electrical wiring must be sized to carry minimum
circuit ampacity marked on the unit.

Use copper conduc-

tors only. Each unit must be wired with a separate branch
circuit and be properly fused.