Checking gas connections, Connecting to gas supply, Warning – Desa CGN18R User Manual

Page 15

Advertising
background image

15

099434

IMPORTANT:

Hold pressure regulator with wrench when connecting it to gas piping

and/or fittings.

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test

Gauge

Connection *

Sediment

Trap

Tee Joint

Pipe

Nipple

Cap

Manual
Shutoff
Valve *

1/2" NPT
Pipe Nipple

Heater
Cabinet

Pressure
Regulator

Figure 12 - Gas Connection

* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See Accessories, page 27.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG

1. Disconnect heater and its individual manual shutoff valve from gas supply

piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or

opening main gas valve located on or near gas meter.

CHECKING

GAS

CONNECTIONS

3" Minimum

Ground Joint
Union

WARNING ICON

G 001

WARNING

Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.

WARNING ICON

G 001

WARNING

Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.

From

Gas Meter

(7" W.C. to 10.5" W.C. Pressure)

CONNECTING

TO GAS

SUPPLY

Continued

Continued