Installation instructions, Warning – Dacor MOV230 User Manual

Page 13

Advertising
background image

11

Installation Instructions

Connecting to a Three Wire Electrical

System - Where Local Codes Permit

WARNING

Do not connect the green appliance conduit wire to the
neutral (white) junction box wire unless local building
codes permit.

Separate the wires coming out of the appliance conduit.

1.

Connect the green and white wires from the appliance

2.

conduit to the white (neutral) supply wire in the junction
box.

Connect the black wire from the appliance conduit to

3.

the black (L1) supply wire in the junction box.

Connect the red wire from the appliance conduit to the

4.

red (L2) supply wire in the junction box.

Conduit from

appliance

Cable from

power supply

Wire nut

(3 places)

Junction

box

RED
RED

GREEN

WHITE

WHITE

BLACK
BLACK

Connecting to a Three Wire Electrical

System with External Ground - Where Local

Codes Permit

WARNING

Do not connect the green appliance wire to the junc-

tion box or to a cold water pipe unless local building
codes permit.

Do not ground the appliance to a gas supply pipe or

hot water pipe.

If connecting the ground wire to a grounded cold

water pipe, connect using a separate copper
grounding wire (No. 10 minimum) and a clamp with
an external grounding screw. The grounded cold
water pipe must have metal continuity to electrical
ground and must not be interrupted by insulating
materials. Any insulating materials must be jumped,
with a minimum, 4 AWG wire to establish continuity
to ground.

NOtE

If the junction box has been properly grounded by a
licensed electrician, the green (ground) wire from the
appliance conduit may be connected to the junction box
using a loop terminal.

See the diagram on the following page. To connect the
green appliance conduit wire to a grounded cold water
pipe:

Separate the wires coming out of the appliance conduit.

1.

Connect the white wire from the appliance conduit to

2.

the white (neutral) supply wire in the junction box.

Connect the black wire from the appliance conduit to

3.

the black (L1) supply wire in the junction box.

Connect the red wire from the appliance conduit to the

4.

red (L2) supply wire in the junction box.

Connect the green wire from the appliance conduit to a

5.

grounded cold water pipe as shown. Jumper any insu-
lating materials as shown above with a length of No. 4
copper wire. Securely clamp the wire to bare metal at
both ends.

Conduit from

appliance

Cable from

power supply

Wire nut

(4 places)

Junction

box

RED

RED

GREEN

GREEN

WHITE

WHITE

BLACK

BLACK

Separate No. 10 (minimum)

copper grounding wire

Clamp must be

tight on pipe

No. 4

copper wire

Metal

water pipe

Clamps

Bare metal

Meter

Advertising
This manual is related to the following products: