4 selecting the timer function – BINDER FED 53 User Manual

Page 27

Advertising
background image

FED (E2) 02/2015

page 27/55

4. Set the required address with buttons

.

You can enter address values between 1 and 30.

The set value is automatically adopted after 2 seconds.

6.4.4 Selecting the timer function

The unit provides three different timer functions:
•

Delayed off (setting “0”)
After the defined time has elapsed, the heating is turned off.

•

Temperature-controlled delayed off (setting “1”)
The defined time only begins to run when the current value is by 1 °C below the set point. After the

defined time has expired, the heating is turned off.

•

Delayed on (setting “2”)
After the time set has passed, the heating is turned on and remain in continuous operation.

1. Press down

button for approx. 5 seconds.

The display alternately shows “unit” and the temperature unit:

2. Press again button

.

The display alternately shows “rASd” and the set-point gradient:



3. Press again button

.

The display alternately shows “Adr” and the unit address:

4. Press again button

The display alternately shows “

tFCt” and the actual setting of the timer function:








5. Set the desired timer function 0, 1 or 2 with buttons

.

The set value is automatically adopted after 2 seconds.

Advertising
This manual is related to the following products: