Troubleshooting flowchart – Computronic Controls Sentry User Manual

Page 6

Advertising
background image

Sentry Iss7 Installation Instructions - December 03 - Page 6 of 6

Is there a standing load

present?

NO

Are electrolyte levels correct?

YES

Are batteries at end of life?

YES

Replace batteries

YES

Is standing load current

greater than charger output

current?

NO

YES

NO

Battery Charger may be faulty

- Contact manufacturer

Top up batteries as per

manufacturers

recommendations

Replace charger with correct

size unit.

Two possible methods:
(1) Using Hydrometer or (2) Using a digital DC voltmeter

Step 1. Fully charge the batteries
Step 2. Disconnect batteries and leads and leave for 24 hours
Step 3. Measure either specific gravity (hydrometer) or terminal voltage
(voltmeter) and compare with table below.

% Charge Specific Gravity Voltage (DC) on a 12V battery
100 1.265 12.8
75 1.225 12.5
50 1.19 12.4
25 1.155 12.0
Discharged 1.12 11.5
If the voltage across the terminals shows around 10.5V, this may indicate
a shorted cell is present.
Step 4. If time is limited due to on-site testing, remove surface charge by
either applying a 20A load for 3 minutes or crank engine for 10 seconds,
then disconnect batteries and leads and leave for minimum of 10 mins.
NOTE: On this method, providing batteries have been sized correctly for
engine and charged correctly, an open terminal voltage of 12.5V or
greater should be present.

Lead Acid

• Physical damage to cells can cause

electrolyte to leak or evaporate

• High charging voltages will evaporate

electrolyte

Check charging voltage against battery type

and voltage

WARNING: If the batteries are being used
at above 20 DEGREES CELSIUS the
chargers output voltage should be
temperature compensated at -3mV/ºC/Cell

The battery charger will need
to provide both the standing
load and minimum charge
current
I.e. if a charging current of 2A
is required, and the standing
load is 1A then the charger
needs to be able to output a
total of 3 amps

REMINDER

FACTORS CONTRIBUTING TO

ELECTROLYTE LOSS

TROUBLESHOOTING FLOWCHART

START HERE

Are batteries charging?

YES

PROBLEM SOLVED

NO

Is a battery charger

connected?

NO

Connect battery charger

YES

Is correct mains supply

present on terminals?

NO

Check mains supply, fuses

and wiring.

YES

Is output voltage correct for

batteries?

NO

Replace with correct voltage

charger.

YES

Is output voltage correct

polarity on terminals?

NO

Check fuses and wiring.

YES

Is battery charger correct size

for battery?

NO

Replace with correct size

charger.

YES

Min Charge Current = AH Capacity of batteries

10

Max Charge Current = AH Capacity of batteries

5

Wet NiCad

Refer to genset manual for sizing of battery chargers to generator set. If
installing your own chargers, battery manufacturers recommend the
following: -
Minimum charge current should be approximately 5% battery AH capacity
Maximum charge current to be equal to 25% battery AH capacity
NOTE: When batteries are normally charged by a charging alternator, a
float battery charger rated at lower than the minimum charge current is
sufficient to keep batteries in fully charged state.

Lead Acid

12V 24V

Float: 13.8V 27.6V
Boost: 14.5V 29.0V

Lead

Acid

12V (10 Cell) 24V (20 Cell)

Float: 14.1V 28.2V
Boost: 14.6V 29.2V

Wet

NiCad

Typical output with no battery or load connected:

SUL & ESUL models - 50% nominal charger voltage

MEASURING CHARGING VOLTAGE AND CURRENT

V

A

CHARGER

+

-

+

-

BATTERY

Figure (ii)

To check charger is working, follow these steps then consult expected conditions
for relevant battery type below.

(1) VOLTAGE - Place voltmeter across battery terminals (V on fig ii)

(2) CURRENT - Break the positive line to the battery and place an ammeter
between positive from charger and positive of battery (A on fig ii)

CURRENT FLOW FROM CHARGER TO BATTERY
If voltage at terminals is less than nominal battery voltage then the maximum rated charger current should
be present.
Note: Once battery is fully charged, output current should be between 0/1% and 0.5% of battery's AH
capacity plus any standing loads.
VOLTAGE RISE AT BATTERY TERMINALS
A gradual rise of voltage should be seen slowing as float voltage is reached. - batteries should NOT be
boost charged continuously (see page 3)
Note: If the battery voltage increases rapidly during charge and no or minimum current is measured then
the battery may have become sulphated and will not hold charge and may be unrecoverable

Lead Acid @ 20ºC

CURRENT FLOW FROM CHARGER TO BATTERY
The current should stay constant or near to constant
whilst charging.

VOLTAGE RISE AT BATTERY TERMINALS
A gradual rise of voltage should be seen until float
voltage is reached, once fully charged a slight drop in
battery voltage will be measured - batteries should
NOT be boost charged continuously (see page 3)

Wet NiCad

Advertising