Metal box controller, Wiring diagram for zone(s) (outputs) – Pinnacle Systems STTS User Manual

Page 21

Advertising
background image

15

WIRING DIAGRAM FOR ZONE(S) (OUTPUTS)

Metal Box Controller

The following examples show two ways to wire a zone: Zone #1 is wired the standard method; Zone #2

is wired for use with external relays. Either of these methods can be applied to any zone.

NOTE: If you use external relays, you must use them on all available zones. You cannot have

external relays on one zone and not on the other zone.

NOTE: If you require 24VDC for power, the transformer SPW626D will be replaced with two chokes.

This modification cannot be performed in the field on the board itself, it must be done at the factory. All

“CE” marked products for the European Community must be 24VDC input power.

Knock out two holes in bottom section of

metal box housing for input power wiring

and alarm zone wiring; minimum hole size

of ½" (13mm). Care should be exercised

in protection of the conductors from

abrasion where they enter the controller

box, with conduit it is accomplished by

bushings or other approved devices. With

NM cable, the outer covering of the cable

should protrude from the clamp to provide

this protection. With armored cable, fiber

bushings are to be inserted between the

conductors and the armor to prevent any

abrasion. All fittings and connectors shall

maintain a NEMA 12 (IP 54) rating at a

minimum.
A. Openings to be closed-where

conductors enter any openings, they shall

be properly closed.

B. When conduit or fittings are used

with open wiring, proper bushings

shall be used.

Advertising
This manual is related to the following products: