Toyotomi FB-38N(FS) User Manual

Page 34

Advertising
background image

15

TEMPERATURE CONTROL (DIFFERENTIAL SWITCH AND DIP SWITCH)


NOE: Make sure that the power supply cord is disconnected when the position of DIP Switch is

selected.


1. The differential switch on the main circuit board controls the heat exchanger water

temperature. The switch can be set at a delta (on/off) of 2°C, 6°C, 9°C or 12°C. A higher
delta reduces burner short cycling.
And you can set the maximum setting temperature at approx. 50°C, 60°C, 70°C or 80°C.

2. The position of DIP Switch is set to 6°C differential from factory. The maximum setting

temperature is set to approx. 80°C at factory. If you like to change the differential, select
the DIP Switch as follows.

HOW TO SELECT DIP SWITCH

NOTE: DIP Switch is located on the main circuit board.

(1)

DIP Switch No. 1: Error history

When turning the DIP Switch No.1 to “OFF” position at the operation
switch off, the burner lamp will flash and it indicates when the error
occurred by number of flashing times and the error code is displayed
on the remote control.

Example:

In case that the error occurred two times before;

1 Error

History

2
3

Differential

4
5

Max. Temp.
Setting

6
7 High

Altitude

8

(2) DIP Switch No. 2 and No.3: Temperature differential

Differential

Dip No.

2°C

6°C

(Factory setting)

9°C 12°C

2 ON ON OFF

OFF

3 OFF ON ON

OFF

(3) DIP Switch No. 4 and No.5: Maximum setting temperature

Set Temp

Dip No.

9 (80°C)

(Factory setting)

8

(70°C)

7

(60°C)

5

(50°C)

4 ON

ON

OFF

OFF

5 ON

OFF

ON

OFF

(4) DIP Switch No. 7: High altitude setting

When using at high altitude (800~1300m), turn the DIP Switch No.7 to
“OFF” position.

This water heater will be not able to be used at more than 1300m
higher altitude.