Installation

(For Qualified Installers Only)

© Travis Industries

4141230

100-01341

Venting the Pellet Insert

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR

INSERT.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
USE AN APPROVED WALL THIMBLE WHEN PASSING THE VENT THROUGH WALLS AND

A CEILING SUPPORT/FIRE-STOP SPACER WHEN PASSING THE VENT THROUGH
CEILINGS (MAKE SURE TO MAINTAIN CLEARANCE TO ANY COMBUSTIBLES).

Maximum Venting Distance:

•

Maximum venting height is 35' (maximum horizontal offset is 10')

•

Use no more than 180° of elbows (two 90° elbows, or two 45° & one 90° elbow, etc.).

Pellet Vent Type

•

Must be Type "L" vent and/or Type "L" chimney liner.

•

3” diameter vent may be used if vent is 20’ or less.

•

4" diameter vent is required if vent height is over 20’.

Installing the Pellet Vent

•

Pellet vent connections must be sealed
airtight with 500° F. RTV silicone and
screwed together with at least three
sheet metal screws.

Pellet Vent Termination

•

Termination must be a minimum 6" above the top of the chimney (NOTE: the chimney must meet
local codes for height above the roof or other obstructions).

•

Must have an approved cap (to prevent water from entering).

•

Must not be located where it will become plugged by snow or other material.

 This fireplace insert must be installed with a continuous chimney liner of 3” or 4” diameter

extending from the fireplace insert to the top of the chimney. The chimney liner must conform to
the Class 3 requirements of CAN/ULC-S636, Standard for Lining Systems for Existing Masonry or
Factory-Built Chimneys and Vents, or CAN/ULC-S640, Standard for Lining Systems for New
Masonry Chimneys.

Seal each vent section (including
adapters, elbows, etc...) by
injecting a liberal amount of 500°
F. RTV silicone into the gap
between sections.

500° F. RTV

Silicone

The exhaust quick-

connect can be

removed to allow for
installation and

cleaning.