Nstallation, Vent requirements, Vent terminations – Avalon Firestyles D-V-1995 User Manual

Page 13: Elbows, Penetration, support parts

Advertising
background image

I

NSTALLATION

(C

ONT

.)

P

AGE

13

Vent Requirements

!

Always maintain the required 1" clearance (air space) to combustible materials to prevent a fire
hazard. Do not fill air spaces with insulation.

!

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.

!

If the stove is installed at an
altitude over 3,000 feet the
flame quality will need to be
carefully evaluated. See
Addendum #1, "Altitude
Considerations", on page 38.

¥

When the vent passes through
a wall, a wall thimble is
required. When the vent
passes through a ceiling, a
support box or firestop is
required. When the vent
passes through the roof, a
roof flashing and storm collar
are required. Follow the
instructions provided with the
vent (from Duravent

) for

installing these items.

Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)

We recommend the use of
the high wind cap (# 991).

Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)

8-5/8"

Maintain a minimum 1"
clearance from vent to
any combustible (vent
is 6 5/8" diameter)

Use a support box
on exposed vent

Vertical Vent

Requirements

Use a wall thimble
whenever passing
through a wall
(Duravent Part #940)

Horizontal
Termination

Maintain a minimum 1" clearance from vent
to any combustible (vent is 6 5/8" diameter)

Minimum
Framing for
wall thimble

Horizontal Vent

Requirements

8-5/8"

Minimum framing
for fire stop

¥

Use Model GS Direct Vent manufactured by Simpson Dura-Vent only (or the Chimney Conversion
Kit - see Addendum #2). Follow the installation instructions included with the vent. For the nearest
Simpson Dura-Vent supplier, call (800) 835-4429. Part numbers and descriptions are listed below.
Straight Lengths

908B

6" Pipe Length, Black (interior)

907B

9" Pipe Length, Black (interior)

906

12" Pipe Length, Galvanized

906B

12" Pipe Length, Black (interior)

904

24" Pipe Length, Galvanized

904B

24" Pipe Length, Black (interior)

903

36" Pipe Length, Galvanized

903B

36" Pipe Length, Black (interior)

902

48" Pipe Length, Galvanized

902B

48" Pipe Length, Black (interior)

911B

11" to 14 5/8" Pipe, Adjustable, Black (interior)

Vent Terminations

981

Snorkel Termination (36" rise)
(for basement or raised
termination installations)

982

Snorkel Termination (14" rise)
(for basement or raised
termination installations)

984

Horizontal Square Termination

983

Vertical Termination

950

Vinyl Siding Standoff

991

High Wind Vertical
Termination

Elbows

990

90¥ Elbow

990B

90¥ Elbow, Black (interior)

945

45

°

Elbow

945B

45

°

Elbow, Black (interior)

Penetration, Support Parts

940

Round Support Box/Wall Thimble

941

Cathedral Ceiling Support Box

943

Flashing, 0/12 to 6/12 Roof Pitch

943S

Flashing, 7/12 to 12/12 Roof Pitch

953

Storm Collar

963

Ceiling Firestop

988

Wall Strap

¥

Apply high-temperature silicone to the male section of inner
pipe (on the lower section of vent) so the silicone seals the
inner pipe from the outer pipe when the sections are
assembled. Slide the sections together and turn 1/4 turn until
the sections lock in place. Install three metal screws through
each joint to lock the outer section in place (see the
instructions included with the vent for further details).

¥

Horizontal sections require a 1/4" rise every 12" of travel

+

Exterior Vent Diameter = 6 5/8", Inner Vent Diameter = 4"

Apply a 1/8" bead of
high-temperature
silicone to the inner
pipe. The silicone
must seal the inner
pipe from the outer
pipe.

Silicone

¥

Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)