N table 3, Table 3 – Basler Electric BE1-50/51B-241 User Manual
Page 18
 
10
9252000792 Rev D
Table 3. Circuit Board Controls
Locator
Description
A
Target Operating Current Jumpers. Two user-adjustable jumpers control the range of trip 
circuit current required to operate the time overcurrent (51) and instantaneous overcurrent 
A (50-A) target indicators. Jumper J1 sets the minimum current range for the 50-A target 
indicator and J2 sets the minimum current range for the 51 target indicator. Two jumper 
positions are possible: across pins 1 and 2 or across pins 2 and 3. When the jumper is 
installed across pins 1 & 2, the targets must operate 
≥ 2.25 A and must not operate < 900
mA. When the jumper is installed across pins 2 & 3, the targets must operate
≥ 200 mA and
must not operate < 80 mA.
B
Four Position Slide Switch. This switch assembly, designated SW3, has four independent 
slide switches designated SW3-1, SW3-2, SW3-3, and SW3-4. Each switch functions as 
follows: 
SW3-1 selects the nominal system frequency. The OFF position selects 60 Hz operation 
and the ON position selects 50 Hz operation. 
SW3-2 provides an additional time delay for the instantaneous overcurrent A (50-A) 
element. The ON position provides an additional delay of 100 milliseconds. 
SW3-3 selects either GE IAC or Westinghouse CO/COM type characteristic curves. The 
ON position selects the GE IAC type curves (listed in Table 4) and the OFF position selects 
the Westinghouse CO/COM type curves (listed in Table 5). 
SW3-4 selects either an instantaneous or integrating time reset characteristic. The ON 
position selects an integrating reset characteristic and the OFF position selects an 
instantaneous reset characteristic. 
C
Instantaneous Overcurrent B Pickup Selector Switches. These two screwdriver-adjusted, 
rotary switches select the instantaneous overcurrent B (50-B) pickup current setting in 
amperes. 
The 50-B pickup switches are accessed on the right side of the draw-out assembly by 
removing the draw-out assembly from the case. 
SW9 is a 16-position switch that sets the units portion (#.#) of the 50-B pickup setting in 
amperes. SW9 setting positions consist of 0 through 9 which correspond to values of 0 to 9 
amperes and A through F which correspond to values of 10 to 15 amperes. SW10 is a 10-
position switch that sets the tenths portion (#.#) of the 50-B pickup setting in amperes. 
SW10 setting positions consist of 0 through 9 which correspond to values of 0.0 to 0.9 
amperes. 
The minimum allowable 50-B pickup setting is 1.0 Aac and the maximum allowable 50-B 
pickup setting is 15.9 Aac. Adjusting the 50-B pickup selector switches while the relay is in 
service may cause the relay to trip. 
Example: SW9 position 2 and SW10 position 5 is a setting of 2.5 Aac. 
 
 
Controls and Indicators
BE1-50/51B-241