Installation, General, Factory settings – Basler Electric BE1-50/51B-241 User Manual
Page 21: Connections
 
9252000792 Rev D
13
Installation
General
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to 
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number 
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that 
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the 
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric, 
Highland, Illinois. 
Proper operation of the relay may be confirmed by performing the operational test procedures of the 
Testing chapter. If the relay will not be installed immediately, store the relay in its original shipping carton 
in a moisture- and dust-free environment. 
Factory Settings
BE1-50/51B-241 jumpers and internal switch SW3 are configured at the factory as follows:
•
SW3-1: OFF (60 hertz operation).
•
SW3-2: OFF (0.0 additional fixed delay for the instantaneous element).
•
SW3-3: OFF (Westinghouse CO/COM type characteristic curves).
•
SW3-4: ON (Integrating reset characteristics).
•
J1 pins 2-3: 50-A minimum target operating current of 80 to 200 mA
•
J2 pins 2-3: 51 minimum target operating current of 80 to 200 mA
Installation
Note
If replacing a CO relay manufactured prior to 1966, please contact 
Basler Electric to verify compatibility. 
Select the desired relay settings before putting the relay into service. Changing pickup current settings 
while the relay is in service may cause tripping. Perform the following steps to install the BE1-50/51B-241 
relay. 
1.
Select the desired relay settings on your new BE1-50/51B-241 relay.
2.
Remove the existing Westinghouse relay cradle.
3.
Insert the new relay cradle and close the cradle latches locking the relay into the case.
4.
Install the cover by positioning the interlocking bracket at the top of the new Basler Electric cover 
into the mating receptacle at the top of the cover adapter plate. Secure the captive fastener at the 
bottom of the cover. 
Connections
Typical ac connections are shown in Figure 7. Typical dc connections are shown in Figure 8.