Characteristic Data

Step 1. Adjust the current source phase angle for each of the values indicated in Table 5-3. Record the

magnitude of current required to receive each pickup indication. To measure pickup for each
phase angle setting, slowly increase the current magnitude from zero or a value less than the
pickup value until the PICKUP LED illuminates and an output contact operation occurs.

Table 5-3. Current Magnitudes Required for Pickup

Current Source Phase

Angle Setting (Degrees)

Equivalent System Power

Factor Angle (Ө) In Degrees

Current Magnitude

Required for Pickup (Amps)

+20

–20

+30

–30

+40

–40

+50

–50

+60

–60

+70

–70

+80

–80

+90

–90

+100

–100

+110

–110

+120

–120

Step 2. With the above recorded data, calculate P (watts) and Q (vars), as follows, for each recorded

pickup value.

( )

θ

cos

3

L

LL

I

V

P

=

( )

θ

sin

3

L

LL

I

V

Q

=

Where:

V

LL

= voltage measured in the test setup of Figure 5-2

I

L

= current measured in the test setup of Figure 5-2

Ө

= the (–) angle setting of the current source

NOTE

With the test setup as specified, the current source phase angle setting simulates

a leading power factor angle, i.e., Ө < 0.

9171500990 Rev N

BE1-40Q Setting and Testing