6.
Verify the corner frequency setting by slowly reducing
the generator frequency until the generator output
voltage just starts to decrease.
If adjustment of the corner frequency is required:
a.
Rotate the Underfrequency control fully counter-
clockwise.
b.
Reduce the generator frequency from nominal
(either 50 Hz or 60 Hz) to the desired corner
frequency.
c.
Slowly adjust the Underfrequency control clock-
wise until the generator output voltage just starts
to decrease.
Figure 1. Potentiometer Controls
Figure 2. Jumper Locations
Figure 3. Frequency Compensation Characteristics