BECKHOFF BK5200 User Manual

Page 15

Advertising
background image

Basic Principles


BK52x0

15

Technical data

LC5200

Number of Bus Terminals

64

Digital peripheral signals

256 inputs/outputs

Analog peripheral signals

Possibility of configuration

Via KS2000 or the controller

Maximum number of bytes

32 bytes input and 32 bytes output

Bus connection

directly to spring-loaded terminals

Power supply

24 V DC (20...29 V DC), via bus cable 11…25V (conforms to DeviceNet
specification)

Input current

70 mA + (total K-Bus current)/4

500 mA max.

Starting current

approx. 2.5 x continuous current

Recommended back-up fuse

≤ 10 A

K-Bus power supply up to

500 mA

Power contact voltage

24 V DC max.

Power contact current load

10 A max.

Electrical isolation

none between power supply/fieldbus/power contacts

Size

similar to the Bus Terminal housing, width 21 mm

Weight approx.

100 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95% , no condensation

Vibrations/Shock resistance

conforms to IEC 68-2-6/IEC 68-2-27

EMC resistance burst/ESD

conforms to EN 50082 (ESD, burst)/EN 50081

Installation position

any

Protection class

IP20



Advertising
This manual is related to the following products: