Natural gas heater vanguard vn6c and vn10, Connecting to gas supply – Desa VN6C User Manual

Page 8

Advertising
background image

8

101851

NATURAL GAS HEATER

VANGUARD VN6C AND VN10

IMPORTANT:

Hold pressure regulator with wrench when connecting it to gas piping and/

or fittings.

Figure 12 - Gas Connection

* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual
shutoff valve from your dealer. See Accessory, page 15.

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test
Gauge
Connection *

Pressure
Regulator

Tee
Joint

Pipe
Nipple

Cap

Manual
Shutoff
Valve *

Ground Joint
Union

Heater
Cabinet

Sediment
Trap

3" Minimum

3/8" NPT
Pipe Nipple

From

Gas Meter

(4" W.C. to
10.5" W.C.

Pressure)

CONNECTING TO
GAS SUPPLY

NOTICE: A qualified service per-
son must connect heater to gas
supply. Follow all local codes.

WARNING: Never connect

heater to private (non-utility) gas
wells. This gas is commonly
known as well-head gas.

IMPORTANT:

Check gas line pressure be-

fore connecting heater to gas line. Gas line
pressure must be no greater than 14 inches
of water. If gas line pressure is higher,
heater regulator damage could occur.

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

Installation must include a manual shutoff
valve, ground joint union, and plugged 1/8"
NPT tap. Locate NPT tap within reach for
test gauge hook up. NPT tap must be up-
stream from heater (see Figure 12).

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

Install sediment trap in supply line as shown
in Figure 12. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Advertising
This manual is related to the following products: