Drolet GTX-I User Manual

Page 26

Advertising
background image

26

III. Main burner will not light

A. Valve / Switches

1. Valve control off

1. Turn to “ON” position

2. Blockage at the burner (line,

orifice, or ports)

2. Check and clean

3. Defective wall switch or

thermostat

3. Conduct a continuity test or jumper wire

test and replace if defective

4. Defective wiring or connections

4. Conduct a test with a jumper wire and

repair as required

5. Excessive length of thermostat

wire from valve to wall switch or
thermostat

5. Reduce wire length to less than 100 feet or

increase wire size

6. Wall switch or thermostat

incorrectly wired

6. Wire correctly

7. Defective Valve

7. Turn valve and “ON/OFF” switch to the

“ON” position. Check with millivolt meter
at terminals TP-TH & TH. Millivolt meter
should read greater then 460 millivolts. If
the reading is OK and the burner does not
come on, replace the gas valve

8. Thermopile may not be

generating sufficient voltage
(460 mV)

8. Recheck using the millivolt meter. The

pilot flame may not be high enough for the
flame to properly engulf the thermopile. If
so, adjust and reset. If voltage is still
insufficient, replace thermopile

9. Wall switch, thermostat, or wires

are defective

9. Follow previous corrective action, check

switch and wiring. Replace where
defective

1. Flame impingement on logs

1. Adjust the log set to avoid direct flame

impingement. Follow log placement
instructions

IV. Soot deposits on glass

2. Improper primary air setting

2. Open aeration shutter more.

3. Foreign material impeding

burner

3. Ensure that no foreign material blocks

burner flame ports

4. Air inlet blocked or restricted

4. Clean air inlets

5. Vent system is restricted or

inadequate

5. Check correct termination is used.

V

.

Flame burns blue and lifts

off burner

1. Insufficient combustion air being

supplied

2. Manifold pressure set too high

3. Vent system restricted

1.Ensure that no foreign material blocks air

inlets and that the burner shutter is
correctly adjusted. Ensure the vent is
adequate

2. Check manifold pressure
3. Check vent system

VI. Flames impinge on firebox

top

1. Vent system is restricted or

inadequate

1. Correct flue as required

2. Manifold pressure too high

2. Check manifold pressure as required

Advertising