Page 20: Horizontal vent installation exterior wall
 
Can
adian Comfort Industries V04
20
PELPRO OWNERS MANUAL
Copyright 2004
www.pelprostoves.com
Dansons Group Inc.
4
18”
8”
6”
Wood Frame
Construction
Stand Offs
Part ACI-3HZ
6”
2” Min.
Air gap
Horizontal Vent Installation
Exterior Wall
Wood Surround
Shroud
3” minimum
air gap
Wall Band /
Support Brkt
every 5’
Clean Out Tee
10’
2’
B
UILT
-I
N
I
NSERT
I
NSTALLATION
 
CAUTION: DO NOT BLOCK VENT OPENING
The PELPRO Insert may be framed directly into a wall as either a horizontal or vertical vent installation see (figure 
27, 28). The exhaust installation requirements are the same as for a freestanding stove. Refer to “Installing your 
Freestanding Stove” for information concerning installation and proper hook-up of the exhaust. 
NOTE: Built-In Installations require Enclosure
Kit #ACI-3HZ Horizontal Vent or #ACI-3VL Vertical Vent.
Dimensions that will be enclosed within the frame work are: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
This example shows the 
exhaust venting out and 
up vertically 
 
Requires Spacer Kit 
#ACI-3HZ 
 
The framed opening for this 
Installation needs to be: 
 
 Tradition Bay View 
Height 21” 
21 - 25”
Width 30”
30”
Depth 17”
17”
 
 
If constructing a chase, adequate 
Insulation, vapor barrier, drywall, 
And caulking must be used. 
 
 
 
FIGURE 27
24”
18 3/4”
Shroud 1”
+
+
6 1/2”
7 3/4”
8 1/4”
3 ½”
Exh au st
Air Inlet
24”
24 3/4”
12 1/4”
10 3/4”
Traditional Insert / Built-In
24”
19”
 -
23”
Shroud 1”
12 1/4”
10 3/4”
+
Exhaust
26”
+
24”
6 ½”
Exhaust
+
Air Inlet
8 1/4”
7 3/4”
3 ½”
Bay View Insert / Built-In
Adjustable
Hopper