Installation sheet, Din rail mount, Derating curves – Crydom CKR Series User Manual

Page 2: Wiring diagram

Advertising
background image

Installation Sheet

DIN Rail Mount

Wire Size

Maximum wire size of AWG #10 (5.3 mm

2

) for input and output terminals.

Connections
Ensure that wires ends are stripped to a minimum length of 0.4 in (10 mm).

Recommended Screw Torque Range
5-6 in-lbs (0.6-0.7 Nm) on input and 10-15 in-lbs (1.1-1.7 Nm) on output terminations.

The following deating curves must be observed before installation.

DERATING CURVES

(B)

Output Current (Arms)

30

25

20

15

10

5

0

20

40

60

80

Ambient Temperature (ºC)

CKRxxx20xxxx

CKRxxx10xxxx

CKRxxx30xxxx

(A)

(B)

The air gap is the clearance distance adjacent to either side of the relay or assembly measured to

the next closer relay or assembly.
100% Duty Cycle.

Rev: 112613

WIRING DIAGRAM

+3/A1 4/A2

1/L1 2/T1

Load

(+/ )

( / )

S O L I D
S T A T E

C O N T A C T O R