Direct-vent fireplace (natural/propane), Fireplace installation, Continued – Desa BDV34NA EN User Manual

Page 20: Installing optional wall mount switch gwms2

Advertising
background image

20

105453

DIRECT-VENT FIREPLACE (NATURAL/PROPANE)

®

FIREPLACE
INSTALLATION

Continued

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close manual shutoff valve (see Fig-
ure 37).

2.

Pressurize supply piping system by ei-
ther opening propane supply tank valve
for propane gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace, or using
compressed air.

3.

Check all joints from propane supply
tank or gas meter to manual shutoff
valve (see Figure 38 for propane or Fig-
ure 39 for natural). Apply commercial
leak test solution to all gas joints.
Bubbles forming show a leak. Correct
all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open manual shutoff valve (see Figure
37).

2.

Open propane supply tank valve for
propane fireplace or main gas valve lo-
cated on or near gas meter for natural
gas fireplace.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 38 for propane or Figure 39 for natu-
ral). Apply commercial leak test solu-
tion to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.

5.

Light fireplace (see Operating Fire-
place
, pages 24 and 25). Check all other
internal joints for leaks.

6.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 24).

Figure 37 - Manual Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Manual
Shutoff
Valve

Figure 39 - Checking Gas Joints for Natural Gas Fireplace

Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane Supply Tank

Gas Valve

Manual
Shutoff Valve

Gas Meter

Gas Valve

Manual
Shutoff Valve

INSTALLING OPTIONAL
WALL MOUNT SWITCH
GWMS2

1.

Connect one terminal of 25 ft. wire for
the wall switch to the TPTH terminal
on the valve. Connect remaining wire
terminal to the TH terminal on the
valve. Make sure that the wire termi-
nals are in the positions on the unit as
pictured in Figure 41, page 21. If wires
are not connected as shown the switch
will not work.

2.

Route the 25 ft. wire through openings
provided on the sides of the fireplace
to a convenient location to mount your
switch.

3.

Connect one bare wire end to each of
the terminals of the GWMS2 Wall
Switch.

4.

Install the wall switch and cover in the
wall.