First Co SHW (2 - 20 Tons) Horizontal Chilled Water User Manual

First Co Equipment

Advertising
background image

The SHW blower coil units are
designed to be installed in a horizon-
tal position with discharge air in a
horizontal direction. The SVW
blower coil units are designed for
installation in a vertical position with
discharge air in a vertical direction.
Both unit models incorporate a posi-
tive slope drain pan with a 3/4" NPT
nipple that exits the unit on the side
of the coil header connections. All
units need to be leveled in such a
way to insure positive slope toward
the condensate drain nipple.
NOTICE: Before mounting unit
remove red headed shipping
bolts and metal bushing at
blower base and blower outlet. In
addition remove, if present, the
wire tie securing motor to blower
rail before operating.
Sufficient clearance must be pro-
vided on the side of the blower coil to
allow access to electrical controls
and to service the motor blower as-
sembly.
Standard unit configuration is right
hand looking with the direction of
airflow. The unit can be field con-
verted to left hand by repositioning
the coil, drain pan and remounting
the motor and pulleys.
NOTE: Motor rotation must be re-
versed. See motor nameplate for
details.

AIR DISTRIBUTION
DUCTS

All duct work must be installed in
accordance with National Fire Pro-

GENERAL

The manufacturer assumes no re-
sponsibility for equipment installed
in violation of any code requirement.
These instructions give informa-
tion relative to the installation of
these blower coil units only. For
other related equipment refer to the
proper instructions.
Material in this shipment has been
inspected at the factory and re-
leased to the transportation agency
in good condition. When received, a
visual inspection of all cartons
should be made immediately. Any
evidence of rough handling or ap-
parent damage should be noted on
the delivery receipt and the material
inspected in the presence of the
carrier's representative. If damage
is found, a claim should be filed
against the carrier immediately.

tection Association Codes 90A and
90B. Ducts should be adequately
insulated to prevent condensation
during the cooling cycle and to mini-
mize heat loss during the heating
cycle. All return air must be filtered
to prevent dirt buildup on the coil
surface. In many cases it is accept-
able to use ducting of the same size
as the blower coil return air connec-
tion. However, unique arrange-
ments or long duct runs must be
confirmed by a local professional.
The manufacturer will not be re-
sponsible for misapplied equip-
ment.

ELECTRICAL

All wiring must comply with local
and national code requirements.
Units are provided with wiring dia-
grams and nameplate data to pro-
vide information required for neces-
sary field wiring. A 4 x 4 electrical
box is provided on the cabinet for
connection of power supply.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

24/36/48/60 SHW / SVW

BLOWER COIL UNITS

***** WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER *****

Altering the product or replacing parts with non authorized factory parts voids all warranty

or implied warranty and may result in adverse operational performance and/or a possible hazard-
ous safety condition to service personnel and occupants. Company employees and/or contractors
are not authorized to waive this warning.

BLOWER COIL UNIT

The installer must adhere strictly
to all local and national code re-
quirements pertaining to the instal-
lation of this equipment.

****** WARNING ******

Unit must not be operated
during building construction
due to excessive airborne
dust and debris. The units
must not be operated under
any circumstances without
an air filter in place.

L45321

3/02

****** WARNING ******

Any devices such as fan
switches or thermostats that
have been furnished by the
factory for field installation
must be wired in strict accor-
dance with the wiring dia-
gram that is supplied with the
unit. Failure to do so could
result in damage to compo-
nents and will void all warran-
ties.

Advertising