Technical data – Flowserve PMV D3 Digital Positioner User Manual

Page 48

Advertising
background image

48

10. Technical data

Rotation angle

min. 30

° max 100°

Stroke

5 - 130 mm (0.2” to 5.1”)

Input signal

4 - 20 mA

Air supply

2 - 7 bar (30 - 87 psi) Free from oil, water
and moisture. Filtered to min. 30 micron

Air delivery

400 nl/min (13.8 scfm)

Air consumption

<0.3 nl/min (0.01 scfm)

Air connections

1/4” G or NPT

Cable entry

3 x M20 or 1/ 2” NPT

Electrical connections

Screw terminals 2.5 mm

2

/AWG14

Linearity

<1%

Repeatability

<0.5%

Hysteresis

<0.4%

Dead band

0.2-10% adjustable

Display

Graphic, view area 15 x 41mm (0.6 x 1.6”)

UI

5 push buttons

Processor

16 bit, M 16C

CE directives

93/68EEC, 89/336/EEC, 92 /31/EEC

EMC

EN 50 081-2, EN 50 082-2

Voltage drop

<10.1V

Vibrations

<1% up to 10 g at frequency 10 - 500 Hz

Enclosure

IP66/NEMA 4X

Material

Die-cast aluminium, A2/A4 fasteners

Surface treatment

Powder epoxy

Temperatur range

–30 to +80

°C (–22 to 176° F)

Weight

D3X, 1.4 kg (3 lbs). D3E, 3 kg (6.6 lbs)

Alarm output

Transistor Ri 1K

Alarm Supply Voltage

8 - 28 V

Advertising