10. Technical data
Rotation angle
min. 30
° max 100°
Stroke
5 - 130 mm (0.2” to 5.1”)
Input signal
4 - 20 mA
Air supply
2 - 7 bar (30 - 87 psi) Free from oil, water
and moisture. Filtered to min. 30 micron
Air delivery
400 nl/min (13.8 scfm)
Air consumption
<0.3 nl/min (0.01 scfm)
Air connections
1/4” G or NPT
Cable entry
3 x M20 or 1/ 2” NPT
Electrical connections
Screw terminals 2.5 mm
2
/AWG14
Linearity
<1%
Repeatability
<0.5%
Hysteresis
<0.4%
Dead band
0.2-10% adjustable
Display
Graphic, view area 15 x 41mm (0.6 x 1.6”)
UI
5 push buttons
Processor
16 bit, M 16C
CE directives
93/68EEC, 89/336/EEC, 92 /31/EEC
EMC
EN 50 081-2, EN 50 082-2
Voltage drop
<10.1V
Vibrations
<1% up to 10 g at frequency 10 - 500 Hz
Enclosure
IP66/NEMA 4X
Material
Die-cast aluminium, A2/A4 fasteners
Surface treatment
Powder epoxy
Temperatur range
–30 to +80
°C (–22 to 176° F)
Weight
D3X, 1.4 kg (3 lbs). D3E, 3 kg (6.6 lbs)
Alarm output
Transistor Ri 1K
Ω
Alarm Supply Voltage
8 - 28 V