5. Function

Signal diaphragm Balance arm

Flapper nozzle

To/from
actuator

Feedback arm

General

The P3 positioner operates on the force balance principle. Changes are initiated by the

signal pressure from the I/P converter. The functionality is described briefly below.

Relay
diaphragm

Signal
pressure

Decrease in signal pressure

When the air pressure on the signal

diaphragm is reduced, the balance arm is
lifted and the flapper nozzle opens. The
pressure on the relay diaphragm is then
reduced and the plug valve upper seal opens
and vents.

Air is now ventilated from the actuator

and its spindle moves. The actuator
movement goes back through the arm
mechanism (see figure) to the positioner
spindle, which rotates the feedback arm. The
balance arm is now lowered by the reduced
spring force and closes the flapper valve. An
equilibrium position is thus reached and the
valve being controlled is in the desired posi-
tion.

Increase in signal pressure

When the air pressure on the signal

diaphragm increases, the balance arm is pres-
sed down and the flapper nozzle closes. The
pressure on the relay diaphragm then
increases and the plug valve opens.

Air is now supplied to the actuator, the

spindle movement rotates the feedback arm,
the balance arm is lifted, and the flapper
nozzle opens. The pressure on the relay
diaphragm is reduced and the plug valve
reduces the air flow to the actuator. An
equilibrium position is thus reached and the
valve being controlled is in the desired posi-
tion.

Single action

Plug
valve

Air
supply

Venting