Wiring – Flowserve TRS5-7 Temperature Switch User Manual

Page 11

Advertising
background image

11

Attention

To protect the switching contacts fuse circuit with T 2.5 A or according
to TRD regulations (1.0 A for 72 h operation).

The screen must not make any other electrical contact.

Note

Connect screen only to terminal [11] and [14] (TRS 5-7b) or terminal
A18 and C18 (TRS 5-7c/d) of the temperature switch.

The rated voltage is stated on the name plate.

When switching off inductive loads, voltage spikes are produced that
may impair the operation of control and measuring systems. Inductive
loads should therefore be provided with commercial arc suppressor
RC combinations, e. g. 0.1 µF/100

.

Wiring

Wiring diagram

For wiring diagram see page 2.

Tool

Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.

TRS 5-7 b

Use screened two-core supply cable for wiring, 2 x 0.35², type K. Max. cable length
100 m. Each temperature switch requires two cables.
The external wire link must be installed afterwards.
1. Connect terminal strip according to wiring diagram. Fig. 1

TRS 5-7 c/d

Use screened two-core supply cable for wiring, 2 x 0.35², type K. Max. cable length
100 m. Each temperature switch requires two cables.
The external wire link must be installed afterwards.
1. Connect terminal strip according to wiring diagram. Fig. 2