Adjust, Temperature limits, Commissioning – Flowserve TRS5-7 Temperature Switch User Manual

Page 12

Advertising
background image

12

Use the code switch at the rear of the TRS 5-7 to adjust the temperature limits.

Adjust

MAX

/

MIN

Temperature Limits

Example

1

Requested temperature limit

τ

max

= 750 °C. The 8-pole code switch shows values

between “5” and “640”. Use a small screwdriver to set the “10”, “20” and “80” and
“640” switches to the right. The sum of the values gives the required temperature
limit

τ

max

= 750 °C

Example 2

Requested temperature limit

τ

max

= 420 °C. Use a small screwdriver to set the “20”,

“80” and “320” switches to the right. The sum of the values gives the required
temperature limit

τ

max

= 420 °C.

Example 3

Requested temperature limit

τ

max

= 146 °C. Use a small screwdriver to set the “5”,

“20”, “40” and “80” switches to the right. The sum of the values gives the required
temperature limit

τ

max

= 145 °C. An exact adjustment of 146 °C is not possible as

temperatures limits can only be adjusted in steps of 5 °C.

Tool

Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.

Switch on mains voltage. The green LED will be illuminated. Fig. 3, Fig. 7

Commissioning

Check whether the TRS 5-7 has been wired to its associated system components
TRG 5-... according to the wiring diagram. Fig. 1, Fig. 2 and Fig. 9.

Check wiring

Apply mains voltage