Key wiring – Flowserve NRG 16-11 User Manual

Page 15

Advertising
background image

5

1

Flange PN 40, PN 63, PN 60, DN 50, DIN 50-

Flange PN 40, PN 63, PN 60, DN 00, DIN 50-

2

For the approval of the boiler standpipe the relevant regulations must be considered.

3

Vent hole

Provide bore as close as possible to the boiler wall!

4

High water HW

5

Electrode rod d = 8 mm

6

Protection tube DN 80

7

Protection tube DN 00

8

Electrode distance

4 mm

9

Low water LW

0

Reducer DIN 66-, K-88.9 x 3. – 4.4 x .6 W

Key

Wiring

NRG 1...-11

Note that screened four-core cable, e. g. I-Y(St)Y  x  x 0.8 or LIYCY 4 x 0.5 mm² is required for wiring

the electrode.

Max. length 00 m with conductivites from 0

µS/cm.

Max. length 30 m with conductivites from 0.5

µS/cm.

Max. length 5 m with conductivites from 0.5

µS/cm and application of the ancillary unit URN 

(4 V DC).

. Unscrew screw

K

,

Fig. 9

. Take the terminal box off the level electrode, leaving the sealing element

O

on the contact

plate

P

.

3. Remove lid

L

.

4. Press connecting plate

N

out of the upper part of the terminal box

M

.

The upper part of the terminal box can be turned in steps of 90°.
5. Detach cable gland

Q

and cable clamp

R

from the upper part of the terminal box

M

.

6. Run cable through cable gland

Q

and upper terminal box

M

and connect the terminals of the

connecting plate

N

according to the wiring diagram.

7. Press connecting plate

N

into the upper part of the terminal box and align the cable.

8. Hold cable with cable clamp

R

and cable gland

Q

in position.

9. Mount lid

L

and insert screw

K

.

0. Put upper part of the terminal box onto the level electrode and fix it firmly with screw

K

.