Basic settings, Switching controller level electrode, Fig. 14 – Flowserve NRG16-41 User Manual

Page 21: Attention, Factory set default node ids

Advertising
background image



Basic Settings

continued

H

1

1

2

2

3

3

1 2 3

5 6 7

4

8 910

ON

1

2

3

4

5

LW HW

Fig. 14

Attention

Do

not assign the same node ID twice within the CAN bus network.

Assigning / changing node ID

If several systems of the same kind are to communicate in one CAN bus network, be sure to assign

one node ID for each individual system component (e. g. controller).
. Undo and remove screws

H. Remove housing cover J.

. Set code switch

M to the required position. Please observe the setting tables on page .

3. Mount housing cover

J and tighten screws H.

M

Factory set default node IDs

NRS 1-40 ID: 001

NRS 1-40.1 ID: 001

NRS 1-41 ID: 006

NRS 1-42 ID: 020

NRS 2-40 ID: 039

NRR 2-40 ID: 040

LRR 1-40 ID: 050

NRG 16-40 ID: 002

NRG 16-40 ID: 003

NRG 16-41.1 ID: 004

TRV 5-40

ID: 005

NRG 16-41 ID: 007

NRG 16-42 ID: 021

NRG 26-40 ID: 041

LRG 16-40 ID: 051

Switching Controller

Level Electrode

Advertising