2003, Flowserve Corporation, Printed in USA

AXAIMO35-0 (AUTO-111)

07/03

3-Position Control/Dribble Control

SR Limit Switch Method

Automax Valve Automation Systems

Installation, Operation and Maintenance Instructions

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663

Cookeville, TN 38501

www.flowserve.com

Phone: 801 489 8611

Phone: 931 432 4021

4-way Valve (Double-acting Actuators)

When operator is energized, the spool shifts, driving the
actuator CCW. When de-energized the spool returns,
driving the actuator CW. For de-energized CCW, rotate
directional valve 180

°

, so that operator points left.

Temperature: NEMA 4X: -20

°

F to 150

°

F

NEMA 4X, 7 & 9: -20

°

F to 125

°

F

For temperatures below 40

°

F, air must

be free of water vapor.

Pressure:

Minimum: 35 psig
Maximum: 150 psig

Media:

Dry or lubricated non-corrosive gas
compatible with nitrile seals.

C

V

= 1.8

Flow Schematics:

(Port 1 - air supply)

3-way Valve (Spring Return Actuators)

When operator is energized, the spool shifts allowing
the air pressure to enter the actuator and compress the
springs. When de-energized, the spool returns,
exhausting the air.

• Coil is U.L. and C.S.A. recognized
• Standard 1/2" NPT connector meets

NEMA 4X rating

• Optional DIN connector for wiring with

3 lead, 18ga cord available. Eliminates
junction boxes at solenoid. Simply plug in
and tighten screw for easy installation
and service

• Standard with non-locking override
• Continuous duty molded class H coil
• 24" electrical leads
• External air pilot

NEMA 4X, 7 & 9 "Explosion-proof"

• 1/2" NPT conduit
• 24" electrical leads
• Meets U.L., C.S.A. and NEMA require-

ments for Class I, Gr C & D Div. 1 & 2
Class II, Gr E, F & G Div. 1 & 2

• Standard with non-locking override
• Continuous duty molded Class B Coil
• External air pilot

Solenoid Electrical Characteristics
Characteristics for standard coils are shown below.
All common voltages and hertz are available.

Weatherproof intrinsically-safe/low power
A .67 watt coil is available with 1/2" NPT weatherproof
housing. The operator has Factory Mutual Entity approval.
See the separate I.S. operator I.O.M. for further information.

The Automax NAMUR Directional valve mounts
directly to SuperNova series actuators which
eliminates the cost of tubing and fittings. The valves
are available for double acting and spring return
actuators with NEMA 4, 4X, 7 & 9, weatherproof
intrinsically-safe, and low power solenoid operators.
These valves have been tested and proven reliable
for over 1 million cycles.

Options:
Dual coil 2-position and 3-position valves are available.
Consult factory.
Sandwich NAMUR mount accessories:
APS1 - Air purge system to purge spring chambers

with solenoid valve exhaust.

Operation

Solenoid will not shift without backpressure on ports
2 and 4. Air supply lines to the valve must have I.D.
at least as large as the NPT size of valve ports.

Solenoid Information

NEMA 4X Weatherproof

AC VOLTAGE

±

10%

DC VOLTAGE

WEATHERPROOF

120 VAC

240 VAC

12 VDC

24 VDC

Inrush Amps

0.078

0.041

0.400

0.200

Holding Amps

0.058

0.030

0.400

0.200

Resistance (

)

840

3310

31.6

121

EXPLOSION-PROOF

Inrush Amps

0.127

0.063

0.632

0.320

Holding Amps

0.057

0.038

0.632

0.320

Resistance (

)

475

2000

19.0

75

Page 1 of 2

FC1, FCSR and FCDA - Single port and dual port

exhaust flow controls.

LV1 - Lockout and vent valve for lockout and

manual override applications.

Automax sandwich NAMUR mount accessories provide compact,
clean control packages for the SuperNova actuator.

S25N NAMUR Directional Valve

3

1

5

2

4

3

1

5

2

4

(Auto-111) S25N IOM