Installation Instructions

The Automax S25N directional valve is installed very
easily to any SuperNova series actuator.

1. Place the gasket seal provided into the gasket bore on the face

of the valve. The gasket seal should be completely seated in the
bore.

2. Place the actuator with the two ports facing you, and the pinion

pointing up. Orient the Automax solenoid valve with the gasket
seal toward the actuator and the operator towards the right.

3. The valve is then mounted to the actuator with the two screws

provided. Apply Loctite Threadlocker 222 or equal to the screws
prior to assembly.

4. Connect the air supply to port #1 and wire solenoid per local

and national electrical codes. The assembly is now ready for
operation.

5. Optional porous bronze vents (P/N 101602) or adjustable

speed controls (P/N 100531) can be added to ports #3 & #5.

6. The S25N directional valve is easily converted from 4-way to

3-way configuration (see figures below right). With the NAMUR
interface facing forward, move the conversion plug from the
left to righthand port to convert to 3-way configuration.
The flathead screw will lift conversion plug out of port.
Tighten screw to secure

conversion plug.

Ordering Example: Automax 4-way solenoid valve with NEMA 4X, 7 & 9 operator, spring return,
120 VAC / 60 HZ would be: S25NAAXR1

For other options - consult factory.

Automax S25N
Spool Type

Body Type

Operator Spring

Voltages

A- 2-position 4-way

A- single operator

A - Remote air pilot D - 3 position spring center

1- 110/50, 120/60

F- 2-position 3-way

B- dual operator

W - NEMA 4X R - 2 position spring return

2- 220/50, 240/60, 120 VDC

C- 3-position 4-way -

X - NEMA 4X, 7 & 9

Repeat operator code for

3- 12 VDC, 22/50, 24/60

blocked center

N - Intrinsically Safe

2 position, dual operator

4- 24 VDC

D- 3-position 4-way

V - 1.8 Watt Low Power

exhaust center

NEMA 4X, 7, & 9

Ordering Guide

Lubrication:

• Lubrication of Automax products is not required

but is recommended to maximize service life. Where
devices not made by Automax are used in the system
the manufacturer should be consulted regarding their
lubrication requirements.

• Lubricators should be installed downstream of regulators

per the manufacturer's instructions.

• Automax positioner supply air must be clean, dry and

oil free. Do not use lubricators in conjunction with
Automax positioners.

• Oils used in air line lubricators should be compatible with

seals used in the system. Generally Automax products use
Buna-N (Nitrile) with Viton seals available as an option.
Oils should be petroleum based with oxidation inhibitors,
an ISO 32 or lighter viscosity, and an aniline point between
82

°

C (180

°

F) and 104

°

C (220

°

F).

Note: See appropriate IOM's for installation of
sandwich NAMUR mount accessories.

4-way Configuration

3-way Configuration

SuperNova
Actuator

24" Leads

M5 x 40mm

Socket Head Cap Screws

Air Supply

(Port #1)

1/4˝ NPT

Port #5

Port #3

Gasket Seal

(p/n 110483)

Coil

(as specified)

(Auto-111) S25N IOM

7/23/03, 2:21 PM

2

Advertising