Operation

(as viewed from top of actuator)

Double Acting

Applying air pressure to Port 1 drives the pistons

Applying air pressure to Port 2 drives the pistons

outward, which turns the pinion counterclockwise as

inward, which turns the pinion clockwise as the air

the air volume on the outside of the pistons exhausts

volume on the inside of the pistons exhausts through

through Port 2.

Port 1.

Spring Return (Fail CW)

Applying air pressure to Port 1 drives the pistons

Exhausting the air pressure from Port 1 allows

outward, which compresses the springs and turns

stored energy of the springs to drive pistons inward,

the pinion counterclockwise as the air volume on the

turning the pinion clockwise. Air volume on outside

outside of the pistons exhausts through Port 2.

of pistons vents through Port 2.

Spring Return (Fail CCW)

Applying air pressure to Port 1 drives the pistons

Exhausting the air pressure from Port 1 allows stored

outward, which compresses the springs and turns

energy of the springs to drive pistons inward, turning

the pinion clockwise as the air volume on the outside

the pinion counterclockwise. Air volume on outside of

of the pistons exhausts through Port 2.

pistons vents through Port 2.