Problem

Output is not continuous throughout actuator/valve stroke
(experience a band of max. output)

Transmitter does not out 4 or 20 mA at desired end of
travel.

Transmitter module does not provide current signal or
provide constant signal.

Output not linear or does not track valve position/rotation

Probable Cause/Solution

Potentiometer is out of adjustment (see “Resistive
Feedback Calibration” or 4-20mA Current Transmitter
Calibration” steps 2-4).

Zero or span trim potentiometer is out of adjustment (see
4-20mA Current Transmitter Calibration).

Circuit Board LED not lit:
1. Loose or shorted signal connection (no loop power).
2. Controller board not responding (replace board)
Circuit Board LED lit:
1. Potentiometer disengaged.
2. Defective potentiometer or controller board. Replace
defective component.

Input signal not linear. Linkage or drive mechanism is
introducing non-linearity. Zero span trim potentiometer is
out of adjustment (see 4-20mA Current Transmitter
Calibration).

Troubleshooting

Figure 1 – 4-20 mA Transmitter Diagram