Operation, alarm and test, Troubleshooting – Flowserve NRS 1-50 For TWO Electrodes User Manual

Page 20

Advertising
background image

0

Operation

Activity

Indication

Function

Level electrode(s) submerged.

Green LEDs for level

electrode  /  illuminated.

Output contacts are closed.

Signal outputs  /  open.

Alarm

Level electrode(s) exposed,

level below low water level

(LW).

Red LEDs

for level electrode  /  are

flashing.

De-energizing delay is running.

Signal outputs  /  are closed instantaneously.

Red LEDs

for level electrode  / 

illuminated.

Delay time has elapsed, output contacts open.

Signal outputs  /  are closed.

Test channel 1 and 2

During operation:

Press key  or  and hold it

down until the end of the test,

level switch must react as if

there was an alarm.

Red LEDs

for level electrode  /  are

flashing.

Alarm simulated in channel  or .

De-energizing delay is running.

Signal outputs  /  are closed instantaneously.

Red LEDs

for level electrode  / 

illuminated.

Delay time has elapsed, output contacts open.

Signal outputs  /  are closed.

Test finished.

Operation, Alarm and Test

Indicators and adjustors

Fig. 14

Attention

Before carrying out the fault diagnosis please check:
Mains supply:

Is the level switch supplied with the mains voltage specified on the name plate?
Wiring:

Is the wiring in accordance with the wiring diagram and the relevant schematic

representation of arrangement?
Configuration: Are the code switch settings

4

and

5

correct for the number of level

electrodes used?

LED alarm  /

operating mode

Level electrode 1

Test & diagnosis

button

LED alarm  /

operating mode

Level electrode 2

Test & diagnosis

button

Diagnosis LED

Troubleshooting

Indication, diagnosis and remedy