Emergency operation – Flowserve NRS 1-50 For TWO Electrodes User Manual

Page 23

Advertising
background image

3

Emergency operation

Emergency operation for water level limiter

If the level switch NRS -50 works with two level electrodes NRG ...-50 (water level limiter to TRD

604, EN 95-07, EN 953-06), the installation can continue operating in emergency operation

mode according to TRD 40 and EN 95 and EN 953 under constant supervision with

only 1 level

electrode, in case that one of the two installed level electrodes fails.
If only one electrode is used for operation change the settings as follows:

n

Switch off mains voltage.

n

Unscrew the right and left fixing screws

3

and remove the lower terminal strip

2

,

Fig. 6

n

Depending on which electrode shall be deactivated, set S or S of code switches

4

and

5

to ON.

n

Attach lower terminal strip and fasten fixing screws.

n

Apply mains voltage, equipment is re-started.

Attention

n

Record the beginning of emergency operation in the boiler log.

n

An installation operating in emergency mode has to be constantly supervised.

n

Immediately replace faulty level electrode.

n

Record the end of emergency operation in the boiler log.

n

When the emergency operation is over, restore original settings.

Code switch

4

Code switch

5

S 

S 

S 

S 

Level electrode  activated

OFF

OFF

Level electrode  deactivated

ON

ON

Level electrode  activated

OFF

OFF

Level electrode  deactivated

ON

ON

4

Toggle switch, white

5

Toggle switch, white

If faults occur that are not listed above or cannot be corrected, please contact our service centre or

authorized agency in your country.